Power of Permanently Installed HFCT Sensors for PD Detection

  • 14 March 2025

  • Thomas Whyte

Articles

As online partial discharge (PD) detection becomes a standard practice in the electrical industry, more networks are investing in sensor technology that enables continuous condition monitoring without supply interruptions.

One effective method is the application of permanently installed High-Frequency Current Transformer (HFCT) sensors. Traditionally, HFCT sensors are clamped around the earth screen of a high-voltage (HV) termination and used to detect PD in both switchgear and HV cables.

However, accessibility to the HV earth screen presents a challenge. In many modern switchgear designs, HV terminations are earthed within the cable chamber, limiting direct access to the attached HFCT. To overcome this, many companies are opting for permanently installing HFCT sensors within the cable chamber.

Figure 1: Permanently Installed HFCT On-Site

HFCT In Use

Benefits of Permanently Installed HFCT Sensors for High-Voltage Networks

1. Enhanced Accuracy in PD Detection

When permanently installing HFCT sensors, it is essential to consider their integration into an existing partial discharge testing program. For point-in-time testing, where switchgear and cables undergo annual PD assessments, HFCT sensors enhance testing accuracy by providing consistent and repeatable data.

This enables asset managers to design targeted test programs focused on either HV cable runs or associated switchgear, ensuring a more precise evaluation of network health. 

For more details on how our Partial Discharge Detection Services can help safeguard your network, explore our solutions.

Integrating High-Frequency Current Transformers into PD Testing Programs

When HFCT installations are widespread, they enable online cable mapping, providing a comprehensive assessment of HV feeder health. By mapping entire feeders, asset managers can generate a network heatmap, allowing for better localisation of PD defects and a more strategic approach to maintenance planning.

2. Consistent and Repeatable Data for Condition Monitoring

 A key advantage of permanently installed HFCT sensors is their ability to provide consistent and repeatable measurements, which significantly enhances partial discharge (PD) detection accuracy. Since HFCT sensors continuously monitor high-voltage (HV) systems, they reduce the risk of false positives by differentiating between actual PD activity and external noise or transient signals. This ensures that asset managers can rely on precise data to make informed decisions about network maintenance.

By maintaining a steady flow of high-quality data, HFCT sensors enable asset managers to conduct accurate PD trend analysis over time, allowing them to predict potential failures and optimise maintenance schedules. This level of consistency improves diagnostic control and helps avoid unnecessary interventions, ultimately enhancing overall network reliability and reducing operational costs.

By integrating HFCT sensors into a routine condition monitoring program, asset managers can collect consistent, high-quality data, facilitating accurate PD trend analysis over time.

For insights into how Condition Monitoring Services enhance network reliability, check our solutions.

HFCT installation

Network Case Study: Real-World Impact of HFCT Sensor Monitoring

A network operator used this methodology to test 191 33kV cables with the EA Technology Cable Data Collector. The results were categorised as:

  • Green: No PD detected
  • Amber: PD detected; retesting recommended in 6 months
  • Red: High PD levels, indicating significant degradation

Over a two-year monitoring period:

  • 41% of cables in the red category and 21% of cables in the amber category experienced failures.
  • Only 1.9% of cables in the green category failed.

HFCT-based testing percentage of cable faults

These findings confirm that HFCT-based testing provides high-quality condition monitoring data, empowering asset owners to prioritise maintenance and replacement plans, enhance network reliability, and reduce maintenance costs.

Using HFCT Sensors for Continuous PD Monitoring and Critical Asset Protection

3. Real-Time Data for Informed Decision-Making

Beyond periodic testing, permanently installed HFCT sensors enable continuous monitoring of known PD sources and provide network-wide risk reduction when installed at primary substations. By integrating an Astute Monitor as the data capture device, asset owners can track real-time PD trends, ensuring early identification of evolving defects before they lead to failures.

The true value of HFCT monitoring lies in its ability to provide detailed waveform analysis, allowing asset managers to differentiate between PD types, severity levels, and defect locations. By examining PD waveform characteristics—such as pulse magnitude, repetition rate, and phase-resolved patterns—it is possible to distinguish between internal, surface, or corona discharge and assess the progression of degradation over time.

4. Optimised Outage Planning and Maintenance Strategies

When applied to a known PD source, real-time data significantly improves outage planning. Asset managers can closely monitor the degradation rate of identified issues, allowing them to adjust maintenance schedules—either accelerating planned outages to prevent failure or deferring work if conditions remain stable. This data-driven approach helps optimise maintenance resources while improving network reliability.

Learn how our advanced Cable Testing Services can safeguard your HV network.

Proactive Maintenance with 24/7 HFCT Sensors for Critical Asset Monitoring

Proactive Maintenance with 24/7 HFCT Sensors for Critical Asset Monitoring

5. Early Detection of Emerging PD Defects

Long-term monitoring of critical assets also makes it possible to detect early-stage degradation that might otherwise go unnoticed. In the initial phase of deterioration, some PD issues are only active for minutes or hours per day, making them difficult to capture through periodic testing alone. A 24/7 monitoring system ensures these intermittent issues are identified early, allowing them to be trended and analysed until they reach a stage where intervention is required.

6. Cost-Effective Network Management and Reduced Failures

This proactive approach supports optimised maintenance strategies, ensuring repairs are timely yet cost-effective, ultimately reducing overall network maintenance costs while enhancing asset longevity.

Conclusion: Why HFCT Sensors Are Essential for High-Voltage Networks

Permanently installed HFCT sensors provide a cost-effective solution for detecting and monitoring partial discharge in high-voltage networks. By enabling both periodic testing and continuous monitoring, they enhance asset reliability, reduce failures, and support proactive maintenance—ensuring a smarter, more resilient power network with optimised operational efficiency.

Secure Your Network with HFCT Sensor Technology

Enhance your network’s reliability by integrating HFCT sensors into your condition monitoring program. Explore our Partial Discharge Testing Solutions to safeguard your high-voltage assets.

Contact us today to discuss your specific requirements and take the first step towards a more resilient power network.

Frequently Asked Questions (FAQ)

1. How do HFCT sensors improve partial discharge monitoring?

HFCT sensors detect partial discharge activity by capturing high-frequency signals emitted during electrical insulation breakdown, allowing asset managers to identify, assess, and mitigate defects effectively.

2. What are the advantages of permanently installed HFCT sensors?

Permanently installed HFCT sensors provide continuous condition monitoring, early defect detection, reduced false positives, and cost-effective network management.

3. How does continuous monitoring with HFCT sensors reduce failure risks?

By offering real-time data on PD activity, continuous monitoring helps identify potential failures early, allowing asset managers to schedule timely maintenance and avoid unexpected outages.